STANDARDS
IEC 60502
NFC
APPLICATION
U-1000 R2V cables can be used in all low voltage power installations. Multiconductors cables are adapted
to remote control and telecontrol installations.
In case of high ambiant temperature, use correction coefficient.
INSTALLATION
These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly
with extra mechanical protection.
Cross sections 1,5 - 2,5 and 4 mm² have to be of class 2 flexiblility, if the cable is connected to equipment
subject to vibration.
Voltage: 0.6/1 kV
Copper conductor: Class 1 up to 6 mm² and Class 2 for the remaining
Insulation: PEX
Outer sheath: PVC
Maximum permanently operating conductor temperature: 90º C
Design standard: XV/RV - IEC 60502-1 & UNE 21123; XV/U-1000 R2V - IEC 60502-1 &
XP C 32331
Application: For use in low voltage power distribution in fixed indoor and outdoor
installations.
Note: Cables up to 16 mm2 cross-sections, inclusive, are manufactured according
standard IEC 60502-1.